TE/XGA SERIES
TE/(x)XGA/(zz)
X = VOLTAGE CODE
ZZ = OPTIONS
The TE/XGA Series is a modular parallel suppressor designed for service entrance or downstream panelboard applications. The TE/XGA is a multi-stage suppression circuit consisting of field proven, fast acting, 40mm MOVs. A surge suppression path is provided for
each mode (L-N or L-L, L-G, N-G) guaranteeing continuous service. Each surge suppression mode is individually fused and utilizes APT’s Patent Pending TranSafe ™ circuitry with thermal cutout to ensure safe operation during severe over-voltages and high fault current
conditions. The suppression elements are encapsulated in UL Listed and Patented Ceramgard ® providing another level of safety. A filter network is added to provide wave shape smoothing and a high level of EMI/RFI noise attenuation.
On-line diagnostics continuously monitor the
unit status and feature redundant LEDs to signal a reduction in surge capacity or loss of a suppression circuit. An audible alarm with test and silence features is included in the standard diagnostic package. All APT products are designed and tested in accordance with the
recommendations and procedures of ANSI/IEEE C62.41 and C62.45. The TE/XGA is UL 1449 Second Edition Listed, and qualified for service entrance applications under Section 37.3 for their most severe, 25kA, fault current test.
Design Features
| Individually Fused Suppression Modes |
| Thermal Cutout |
| Copper Bus Bar Connection |
| Solid State Bi-directional |
| Front Panel Alarm with Test/Silence Switch |
| Operational Indicators (LED) to Indicate Loss of Protection or Circuit Fully
Operational including N-G |
| High Energy Parallel Design for Category A, B and C3 Applications
For External Mounting next to Panelboards, Switchgear, or Motor Control Centers
| AC Tracking Filter with EMI/RFI Filtering Up to -50dB from100kHz to 100MHz
| |
Quality
| Five Year Warranty: Includes Unlimited module replacement
| Burn-in Tested Prior to Shipment
| Short Circuit Withstand Tested to 100KAIC
| Patent Application Pending
| TranSafe TM Circuit Design Utilizing Surge Rated Fusing and Thermal Cutout
| | | | |
Performance Features
| Surge Capacity L-N L-G N-G
160kA/phase 80k 80k 120k
240kA/phase 120k 120k 120k
| UL 1449 Second Edition Listed, 1283 |
| Recognized, and CUL |
| 200K AIC Rated Fusing
| Less than 1/2 Nanosecond Response Time
| 5000 Category C3 Impulses with <10% Drift
| | | |
Environmental Features
| Relative Humidity Range: 0 - 95% Non-Condensing
| Operating Frequency: 47 - 63 Hz
| Operating Temperature: -0oC to +65oC
| External Mount NEMA 1 Standard (Other NEMA enclosures are available)
| Standard Size: 12"x12"x6" (LxWxD)
| Weight: 25 Lbs. |
| | | | |
Model |
Service Voltage |
L-N |
L-G |
N-G |
L-L |
MCOV |
TE/1XGA |
120/240V Split Phase |
330 |
330 |
330 |
700 |
150 |
TE/11XGA |
120V Single Phase |
330 |
330 |
330 |
|
150 |
TE/12XGA |
240 Single Phase |
600 |
600 |
600 |
|
275 |
TE/2XGA |
120/208V 3-Phase, Wye |
330 |
330 |
330 |
700 |
150 |
TE/3XGA |
120/240V 3-Phase hi-leg Delta |
330/
700 |
330/
700 |
330 |
700/
1200 |
150/
275 |
TE/4XGA |
277/480 3-Phase WYE |
700 |
600 |
600 |
1200 |
320 |
TE/5XGA |
480V 3-Phase De;ta |
|
1500 |
|
1500 |
575 |
TE/51XGA |
480V 3-Phase corner grnd Delta |
|
1500 |
|
1500 |
575 |
TE/6XGA |
240V 3-Phase Delta |
|
700 |
|
700 |
275 |
TE/61XGA |
240V 3-Phase Corner grnd Delta |
|
700 |
|
700 |
275 |
TE/7XGA |
220/380V 3-Phase Wye |
700 |
600 |
600 |
1200 |
320 |
TE/8XGA |
347/600V 3-phase Wye |
1000 |
1000 |
900 |
1800 |
420 |
TE/9XGA |
600V 3-Phase Delta |
|
1500 |
|
1800 |
750 |
TE/91XGA |
600V 3-Phase corner grnd Delta |
|
1500 |
|
1800 |
750 |
Ordering information for Optional Features should be appended to the model number and seperated by a slash(/).
Example: TE/2XGA/240/DC
/240 Module Option increases the surge current capacity from 160kA/phase to 240kA/phase.
/DS Integral Disconnect Switch when a spare 3 pole breaker is not available for connecting the suppressor, order with an internal disconnect.
[Increases size to 16"x14"x6 (LxWxD)] Other disconnect options available.
/DC The Dry Contacts monitor each phase providing a summary alarm. The contacts are terminated in a DB-9 connector.
/RM Remote Monitor with indicator lights and audible alarm is available for use with the Dry Contact Option.
/SC Surge Counter option monitors the occurrence of transients entering the facility through the suppressor and is supplied with a lithium battery to provide power to counter in the event of a power failure.
/2S Dual LCD Surge Counters (Seperate counter for L-N and L-G modes).
/FM Flush Mount option replaces the standard surface mount enclosure.
/3R NEMA 3R enclosure.
/04 NEMA 4 enclosure.
/4X NEMA 4X enclosure.
/12 NEMA 12 enclosure.
| |