XTE/HP SERIES
XTE/(x)HP/(zz)
X = VOLTAGE CODE
ZZ = OPTIONS
The XTE/HP Series is a modular parallel suppressor designed for service entrance or downstream panelboard applications. The TE/HP is a multi-stage suppression circuit consisting of field proven, fast acting 40mm MOVs. Each surge suppression module
is individually fused and utilizes APT’s Patent Pending TranSafe ™ circuitry with thermal cutout to ensure safe operation during severe over-voltages and high fault current conditions. The suppression elements are encapsulated in UL Listed and Patented Ceramgard ® providing
another level of safety. A filter network is added to provide wave shape smoothing and a high level of EMI/RFI noise attenuation.
On-line diagnostics continuously monitor the unit status and feature redundant LEDs to signal a reduction in surge capacity or loss of a suppression circuit. An audible alarm with test and silence features is included in the standard diagnostic
package. All APT products are designed and tested in accordance with the recommendations and procedures of ANSI/IEEE C62.41 and C62.45. The XTE/HP is UL 1449 Second Edition Listed, and qualified for service entrance applications under Section 37.3 for their most severe, 25kA,
fault current test.
Features
 | Individually Fused Suppression Modules |
 | Thermal Cutout |
 | Copper Bus Bar Connection (1/4" Bus Bar) |
 | Solid State Bi-directional |
 | Front Panel Alarm with Test/Silence Switch |
 | Redundant Operational Indicators (LED) to indicate loss of protection or circuit fully operational |
 | For External Mounting Next to Panelboards, Switchgear, or Motor Control Centers |
Quality
 | Five Year Warranty: Includes unlimited module replacement |
 | Burn-in Tested Prior to Shipment |
 | Short Circuit Withstand Tested to 100KAIC |
 | High Energy Parallel Design for Category C3 applications |
 | AC Tracking Filter with EMI/RFI Filtering up to -50dB from 100kHz to 100MHz |
Performance Features
 | Surge Capacity L-N N-G
|
120kA/phase 120k 120k
160kA/phase 160k 160k
 | UL 1449 Second Edition Listed, 1283 Recognized, and CUL |
 | 200KAIC Rated Fusing |
 | Less than 1/2 Nanosecond Response Time |
 | 5000 Category C3 Impulses with <10% Drift |
Environmental Features
 | Relative Humidity Range: 0 - 95% Non-Condensing |
 | Operating Frequency: 47 - 63 Hz |
 | Operating Temperature: -40oC to +65o |
 | External Mount NEMA 1 Standard (Other NEMA enclosures are available) |
 | Standard Size: 10.75"x10.88"x4.5" (LxWxD) |
 | Weight: 9.5 Lbs. |
Model |
Service Voltage |
L-N |
N-G |
L-L |
MCOV |
XTE/1HP |
120/240V Split Phase |
330 |
330 |
700 |
150 |
XTE/11HP |
120V Single Phase |
330 |
330 |
|
150 |
XTE/12HP |
240 Single Phase |
600 |
600 |
|
275 |
XTE/2HP |
120/208V 3-Phase, Wye |
330 |
330 |
700 |
150 |
XTE/3HP |
120/240V 3-Phase hi-leg Delta |
330/700 |
330 |
700/1200 |
150/275 |
XTE/4HP |
277/480 3-Phase WYE |
700 |
600 |
1200 |
320 |
XTE/5HP |
480V 3-Phase De;ta |
|
|
1500 |
575 |
XTE/51HP |
480V 3-Phase corner grnd Delta |
|
|
1500 |
575 |
XTE/6HP |
240V 3-Phase Delta |
|
|
700 |
275 |
XTE/61HP |
240V 3-Phase Corner grnd Delta |
|
|
700 |
275 |
XTE/7HP |
220/380V 3-Phase Wye |
700 |
600 |
1200 |
320 |
XTE/8HP |
347/600V 3-phase Wye |
1000 |
900 |
1800 |
420 |
XTE/9HP |
600V 3-Phase Delta |
|
|
1800 |
750 |
XTE/91HP |
600V 3-Phase corner grnd Delta |
|
|
1800 |
750 |
Note: XTE 9.91 not available with /CL option
Optional Features
/CL Module Option increases the surge current capacity from 120kA/phase to 160kA/phase.
/DS Integral Disconnect Switch when a spare 3 pole breaker is not available for connecting the
suppressor, order with an internal disconnect.
[Increases size to 16"x14"x6 (LxWxD)] Other disconnect options available.
/DC The Dry Contacts monitor each phase providing a summary alarm. The contacts are terminated in a DB-9 connector.
/RM Remote Monitor with indicator lights and audible alarm is available for use with the Dry Contact Option.
/SC Surge Counter option monitors the occurrence of transients entering the facility through the suppressor and is supplied with a lithium battery to provide power to the counter in the event of a power failure.
/2S Dual LCD Surge Counters (separate counter for L-N and L-G modes).
Ordering information for Optional Features should be appended to the model number and seperated by a slash(/).
Example: XTE/2HP/CL/DS
|