Collmer Transient Voltage Surge Suppressor
Non-UL TVSS Aresters


Part No. Service Voltage AC (RMS) Wire Configuration Typical Clamp Voltage
8x20µs Current Wave (Line to Ground)
HE-300
CS9154A1
120/240
1-phase
175V Max
Line (Black)
Neutral/Ground (White)
1.5kA
500V1
625V2
5kA
650V1
950V2
10kA
750V1
1400V2
20kA
950V1
2200V2
25kA
1050V1
2500V2
HE-600
CS9155A1
120/240
3-phase
175V Max/300V Max
High Voltage Line Red
Line 1 & 2 (Black)
Neutral/Ground (White)
775V1
875V2
500V1
625V2
950V1
1250V2
6501
950V2
1125V1
1750V2
750V1
1400V2
1300V1
2550V2
950V1
2200V2
1425V1
2950V2
<1050V1
2600V2
HE-700
CS9156A1
240
1-phase
300V Max
Line 1 & 2(Black)
Neutral/Ground (White)
775V1
875V2
950V1
1250V2
1125V1
1750V2
1300V1
2550V2
1425V1
2950V2
HE-800
CS9157A1
240
3-phase
300V Max
Line 1, 2 & 3(Black)
Neutral/Ground (White)
775V1
875V2
950V1
1250V2
1125V1
1750V2
1300V1
2550V2
1425V1
2950V2
HE-900
CS9158A1
480
3-phase
550V Max
Line 1 & 2(Black)
Neutral/Ground (White)
1450V1
1550V2
16500V1
2000V2
1850V1
2450V2
2200V1
3400V2
2400V1
3950V2
1 1" leads
2 18" leads

Wiring Diagrams

Installation Instructions


Dimensions: 2 x 2 x 1.5, #12 AWG color coded wires
Technology: Metal Oxide Varistors (MOV) each line to neutral/ground
Peak Surge Curent:25,000 Amps all models
Operating Temperature: -40oC to +85o
Response Time: <5ns
Current Drain: <100µA
Unit Weight:
Shipping Weight:8.5 oz.each; per carton (12) 6.75 lbs.; per case (48) 28.5 lbs.
ANSI/IEEE: C62.11-1987 and C62.41-1991


commomni@aol.com

If you have reached this page through a browser and do not have the "Comm-Omni Navigation Bar" at the top, please follow this link.

Return to Comm-Omni Home Page

Index

To speak to one of our consultants, please call us at 1-800-543-8790