Collmer Secondary Surge Arrestor Series
The Collmer Secondary Surge Arresters are MOV (Metal Oxide Varistor) based, hardwired devices, often referred to as Lightning Arresters. The device is designed to protect electrical equipment from damaging effects of spikes(+) and
Notches(-) caused by lightning, utility switching, insulation arcing, electrical motor cycling, and other large or sudden changes in electrical power flow on incoming AC power lines.
The arresters are available in a number of electrical configurations ranging from 120/240V single phase to 277/480V 3-phase 4-wire systems. These epoxy encapsulated arresters are designed to be easily installed in any position indoors or outdoors utilizing the integral 1/2"
threaded nipple and metal lock nut.
Their flame retardant plastic housing is both weather and UV resistant and complies with the UL standard for strength and flame resistance properties. They are sealed with UL component recognized epoxy potting compound. All leads are 18" long and are color coded 12 AWG gauge
multi-stranded wire.
Collmer arresters are ideal for protecting panel boards, outdoor lightning and pole lamps, workshops, refrigeration systms, farm equipment (including milking machines and poultry processing equipment), electric motors and controls, air conditioning equipment; oilfield,
irrigation, sump and heat pumps and many other electrical devices.
FEATURES:
| Residential/industrial/Commercial
| MOV Circuit design
| Cost effective
| Made in U.S.A.
| Solid-State Protection
| Maintenance Free
| Indoor and Outdoor applications
| Automatic Recovery/Self Restoring
| Single MOV per pole design
| Threaded 1/2" conduit nipple with locknut
| Compact size - 2"H x 2"W x 1.5"D
| 18" stranded 12 AWG color coded leads
| | | | | | | | | | | |
Model HE-500
120/240, single phase, 3-Wire
Part No. |
Service Voltage AC (RMS) |
Wire Configuration |
Typical Clamp Voltage
8x20µs Current Wave (Line to Ground) |
HE-500
CS9150A1 |
120/240
1-phase
175V Max |
Line 1 & 2 (Black)
Neutral/Ground (White) |
1.5kA
500V1
625V2 |
5kA
650V1
950V2 |
10kA
750V1
1400V2 |
20kA
950V1
2200V2 |
25kA
1050V1
2600V2 |
|
Technology: Metal Oxide Varistors (MOV) each line to neutral/ground
Peak Surge Current: (8x20µs) 25,000 Amps
MCOV: 175 VAC rms (L-N)
Wiring: 3-wire
Operating Temperature: -40oC to +85o
Response Time: <5ns
Current Drain: <100µA
Shipping Weight: 8.5 oz each, per carton (12) 6.75 lbs.; per case (48) 28.5 lbs.
Unit Weight: 7.5 oz.
ANSI/IEEE: C62.11-1987 and C62.41-1991
UL: OWHX Secondary Surge Arrester
Model HE-510
120/240V, 1-phase, 3-wire
Part No. |
Service Voltage AC (RMS) |
Wire Configuration |
Typical Clamp Voltage
8x20µs Current Wave (Line to Ground) |
HE-510
CA9151A1 |
120/240
1-phase
175V Max |
Line 1 & 2 (Black)
Neutral/Ground (White) |
1.5kA
500V1
600V2 |
5kA
700V1
975V2 |
10kA
850V1
1450V2 |
20kA
1500V1
2700V2 |
|
Technology: Metal Oxide Varistors (MOV) each line to neutral/ground
Beak Surge Current: (8x20µs) 13,000 Amps
MCOV: 175 VAC rms (L-N)
Wiring: 4-Wire
Operating Temperature: -40oC to +85o
Response Time: <5ns
Current Drain: <100µA
Unit Weight: 7.5 oz.
Shipping Weight: 8.5 oz. each, per carton (12) 6.75 lbs.; per case (48) 28.5 lbs
ANSI/IEEE: C62.11-1987 and C62.41-1991
UL: OWHX Secondary Surge Arrester
Part No. |
Service Voltage AC (RMS) |
Wire Configuration |
Typical Clamp Voltage
8x20µs Current Wave (Line to Ground) |
HE-1203
CS9152A1 |
120/208
3-phase
175V Max |
Line 1, 2 & 3 (Black)
Neutral/Ground (White) |
1.5kA
500V1
625V2 |
5kA
650V1
950V2 |
10kA
750V1
1400V2 |
20kA
950V1
2200V2 |
25kA
1050V1
2600V2 |
|
Technology: Metal Oxide Varistors (MOV) each line to neutral/ground
Peak Surge Current: (8x20µs) 25,000Amps
MCOV: 175 VAC rms (L-N
Wiring: 4-Wire
Operating Temperature: -40oC to +85o
Response Time: <5ns
Current Drain: <100µA
Unit Weight: 8.5 oz.
Shipping Weight: 9.5 each, per carton (12) 7.5 lbs.; per case (48) 31 lbs.
ANSI/IEEE: C62.11-1987 and C62.41-1991
UL: OWHX Secondary Surge Arrester
HE-4803
277/480V 3-phase, 4-Wire
Part No. |
Service Voltage AC (RMS) |
Wire Configuration |
Typical Clamp Voltage
8x20µs Current Wave (Line to Ground) |
HE-4803
CS9153A1 |
277/480
3-phase
550V Max |
Line 1, 2 & 3 (Black)
Neutral/Ground (White) |
1.5kA
1450V1
1550V2 |
5kA
1650V1
2000V2 |
10kA
1850V1
2450V2 |
20kA
2200V1
3400V2 |
25kA
2400V1
3950V2 |
|
Technology: Metal Oxide Varistors (MOV) each line to neutral/ground
Peak Surge Current: (8x20µs)25,000 Amps
MCOV: 550 VAC rms (L-N)
Wiring:4-wire
Operating Temperature: -40oC to +85o
Response Time: <5ns
Current Drain: <100µA
Unit Weight: 8.5 oz.
Shipping Weight: 9.5 each, per carton (12) 7.5 lbs.; per case (48) 31 lbs.
ANSI/IEEE: C62.11-1987 and C62.41-1991
UL: OWHX Secondary Surge Arrester
1 1" leads, 2 18" leads
Wiring Diagrams
Installation Instructions
commomni@aol.com
If you have reached this page through a browser and do not have the "Comm-Omni Navigation Bar" at the top, please follow
this link.
Return to Comm-Omni Home Page
Index
To speak to one of our consultants, please call us at 1-800-543-8790
|
|