SPECIFICATIONS
(overall)
Maximum Let-Thru Voltage (10x1000µs (Occurrences)): >100
Peak Current (8 x 20µs Waveform): 10kA
Maximum Continue Current (ma): 150
Nominal Series Resistance: 5 Ohms
Part No. |
Max Peak
Signal Voltage |
Nominal
Breakdown
Voltage |
Max Let-Thru
Voltage 10x700µs
@400Amps |
Typ Cap
(pf) |
DRS-008 |
6 |
8 |
15 |
1500 |
DRS-015 |
12 |
15 |
20 |
1500 |
DRS-232 |
15 |
22 |
30 |
1500 |
DRS-030 |
24 |
30 |
35 |
1500 |
DRS-036 |
30 |
36 |
45 |
1500 |
DRS-043 |
35 |
43 |
55 |
1500 |
DRS-050 |
43 |
50 |
72 |
800 |
DRS-060 |
52 |
60 |
80 |
800 |
**DRS-130RMS |
170 |
200 |
350 |
1000 |
**For this model only Surge Current: >10, Peak Current: 8kA, Max Continuous Current: N/A; Series Resistance: None. WARNING: For Discrete Signal Use Only. Do NOT use DRS-130RMS on 120VAC poewr lines. This unit is a Non-Hybrid, MOV design,
reated above 5A operational current and can withstand greater than 8 occurrences of a 10kA 8x20µs waveform and greater than 1000 occurrences of a 200A 10x1000µs waveform.
5 Blank numbering tabs and 2 Ground tabs are provided with each DRS. Pre-Numbered Tabs available upon request for a nominal charge.