FIRE & SECURITY SURGE PROTECTORS

HSP-121BT Series


Description

The HSP121BT-1RU is an advanced 3 stage hybrid, solid state power line surge protector. Features such as noise filtering, common mode and normal mode suppression, nanosecond reaction time, power line tracking, and compression screw terminations, make the HSPI21BT-1RU an excellent choice in commercial and industrial applications.

The HSP121BT-1RU offers a replaceable fuse designed to remove the load (protected equipment) from the line if the unit is either overloaded or the internal protection fails. This feature prevents surges from entering equipment through a failed protector, not noticed by the user. Unlike models with only an indicator, which may take weeks to notice, the HSP121BT-IRU demands immediate attention upon the unlikely occurrence of internal failure.

Features Benefits

bulletAutomatic recovery Clamping Cat 330V L-N, 400V L-G
bulletFast response time ANSI/IEEE C62.4 I 1991-Cat. CIIB3
bulletFailure indicator Peak Clamp Voltage 315V L-N, 350V L-G
bulletPower line tracking Max Single Pulse 10kA
bulletFiltering Response Time <5 nanoseconds
bullet3 Stage Hybrid Design Operational Temperature 20oC to +85oC
bulletReplaceable Fuse Failure Indication LED
bulletUL 1449 Recognized Operational Voltage 120VAC, 60Hz.
bulletOperational Current 15 AMPS Service
bulletDimensions 2.87" x 5.25" x 1.75"


SPECIFICATIONS

 Clamping Cat 330V L-N, 400V L-G
ANSI/IEEE C62.41 1991-Cat. C1/B3  
Peak Clamp Voltage 315V L-N, 350V L-G
Max Single Pulse 10kA
Response Time <5 nanoseconds
Operational Temperature -20oC to +85oC
Failure Indication LED
Operational Voltage 120VAC, 60Hz
Operational Current 15 AMPS Service
Dimensions (inches) H x W x L 2.87 x 5.25 x 1.75

Installation

  1. Mount HSP121BT-1RU in a UL Listed Housing
  2. Make sure wiring from power sources properly connects to line side of HSP. Wiring from protected equipment must properly connect to EQUIP side of HSP.
  3. Indication of internal failure:
      a. Indicator will extinguish
      b. Fuse blown will disconnect load from power source.
    WARNING: For continued protection against risk of fire, replace only with same type rating of fuse.
  4. Connect only to 120 VAC, 15 Amp max., single phase, three wire circuit.