EDCO Telecom/Datacom Surge
Protection Products
TS-500
Description
The TS-500 is an advanced, solid-state, power line surge protector. It meets IEEE Category A and B performance and features normal mode clamping, common mode clamping and series thermal fusing.
The special thermal safety feature activates in the rare event of internal component failure. Only excessive heat will activate this feature; not surge. This provides an important safety precaution often overlooked in similar products. The neon lamp, when illuminated, verifies
the power protection is operational. Listed under UL standard 1449.
Features & Benefits
| Designed for Direct Broadcast Systems
| Pay-Per-View, Power, & Video Suppression in One Package
| Five Year Warranty
| Instant Recovery After Surge
| Nanosecond Response Time
| Special Thermal Safety Feature
| | | | | |
MODELS
TS-500 - 120V, 15A TVSS
TS-500G - TS500 w/External Ground
Lug
TS-500T - TS500 w/Phone (RJl1) Line
Protection
TS-500TG - TS500T w/External Ground
Lug
TS-500F - TS500G w/transformer
mounting ability
Specifications - Power Protection
Parameter |
Normal Mode (L-N)
|
Common Mode
|
Response Time |
<5 Nanoseconds |
<5 Nanoseconds |
Maximum Surge Current (8x20 us) |
6,500 Amps |
6,500 Amps |
Thermal Protect Temperature |
+83oC |
N/A |
IEEE 587 Cat B Ring* |
430 |
410V |
UL 1449 Rating |
500V |
500V |
*measured from zero volts, 90o Phase Angle
Continuous Current Rating - 6 Amps
Telephone RJ11/RJ48 Protection
DC Breakover Voltage: |
|
T-R |
300-380V |
T-G |
300-380V |
R-G |
300-380V |
Stand-Off Voltage (min) |
±180V |
Leakage Current (max @ 60 Hz) |
<10ua |
Holding Current (min) |
260ma |
Peak on State Voltage It=1A |
3V |
Response Time |
<1ns |
Peak Pulse Current (10 x 1000us) |
|
Applied between TR, TG, RG |
100A |
Applied simultaneously TG, RG |
200A |
Capacitance (50 VDC Bias) |
<100pf |
Includes 7' cable with male RJ's
comm-omni@comm-omni.com
Return to Comm-Omni Home Page
Index
To speak to one of our consultants, please call us at 1-800-543-8790
|
|