lines with ground rods which will effectively parallel the inductance and reduce the overall system inductance. In some locations it may be necessary to utilize all three of these techniques for the best results. Let’ s examine each one.
Conductor Surface Area
The most effective material for a ground system conductor is copper strap. Copper as a metal is a good electrical conductor, only moderately attacked by ground and air borne acids, and should have a life-span measured in years.
Since lightning has a large portion of its energy in the LF range, it will behave like an RF signal. That means the energy will only be conducted on the skin of the conductor (skin effect). Thus, the surge current will only ride on the outermost surface of the conductor. Such currents following a round-member conductor will not make
extensive use of its large cross sectional area. With a 1-1/2 inch or larger flat strap of at least 26 gauge (0.0159 inches), both surfaces will conduct the surge.
Soil Doping
Water in its purest form is an insulator. Ionic salts when mixed with water make ions. The earth is a conductor because of the number of ionic salts present in the soil. Therefore, conductivity can be improved by adding more ions to the soil.
Soil doping can be done by either adding water or a saline solution to the soil around the grounding system. If the soil already has a sufficient amount of naturally occurring salts, adding water will free the ions and improve conductivity. The more ions (salts) available, the less water that will be needed to reach a given level of
conductivity. If few natural ions are available, salts, such as Epsom salts, can be added to the soil to increase the conductivity.
Depending on the amount of rainfall, doping the ground system radials with 4 pounds of salt per linear foot and 20 pounds per rod may last approximately two years.
Ground Radials
Radials are the most cost effective grounding technique considering system impedance, material cost, and installation labor. If one radial gives "X" resistance, then two will deliver an equivalent "parallel rule" plus 10%. This rule only holds true when the soil has the same conductivity over the entire radial area. After the first two
radials, you will need to double the number of radials each time to continue with the parallel-plus rule.
Radials do have a limit on their effective length. If the surge energy has not been launched into the soil within the first 75 feet, the inductance of the radial will prevent any further effective prorogation. Therefore, as a general rule of thumb, all radials should be at least 50 feet long and no longer than 75 feet.
Previous Page
Next Page