PolyPhaser Grounding Solutions
POLYPHASER EARTHED ENTRANCE PANELS (PEEP)
APPLICATION:
Where coaxial cables enter a facility and both grounding of the outside shield and coaxial surge protectors are desired to protect electronic equipment as well as for establishing a central single point ground location.
| Accommodates up to 3-1/8" rigid line (without FIA flange) and up to EW28 type elliptical line (without flange) including coaxial cables
| Weather-boot protected cable grounding kit
| 6" wide 15' long copper straps provide low inductance, large surface area conductors with sandwich bar connection and joint compound for system lug or exothermic interconnection to the perimeter ground cable
| Boot made of EPDM +300, -60F, excellent UV and atmospheric stability, expands to 200% to fit over cable
| Inside horizontal plates provide sandwich connections to flexible copper straps for grounding the coaxial protectors
| Design allows for various length cable connections to the surge protectors and accommodates cable entry
| Horizontal plates have hole locations for bolting other equipment grounding cables to form a single point facility ground
| | | | | | |
SPECIFICATIONS:
Material: C 110 half hard copper
Hardware: Stainless steel and brass
Boots: UV & weather resistant EPDM rubber
ORDER INFORMATION:
All the parts listed below in black have been replaced by:
5PEEP-M
8PEEP-M
Combinations may be made by multiples of the 5 and 8 port systems.
3PEEP 3 port system, two 6' wide straps
5PEEP 5 port system, two 6' wide straps
8PEEP 8 port system, two 6" wide straps
10PEEP 10 port system, four 6" wide straps (two-5 PEEP)
16PEEP 16 port system, four 6" wide straps (two-8PEEP)
24PEEP 24 port system, four 6" wide straps (three-8PEEP)
comm-omni@comm-omni.com
Return to Comm-Omni Home Page
Index
To speak to one of our consultants, please call us
at 1-800-543-8790
|