TELEPHONE GAS STATION PROTECTOR MODULES
TII 355 MAXIMUM DUTY
TII 356 HEAVY DUTY
TFS® TOTEL FAILSAFE® THREE-ELECTRODE GAS TUBE SURGE PROTECTOR MODULES
(Patent No.4,212,047)
UL Listed CSA Certified REA Accepted
The totally encapsulated TFS® Totel Failsafe ® modules protect against both longitudinal and metallic surges by grounding both sides of the pair simultaneously when a surge arrives on either side of the pair. After the surge is
cleared the protector resets to its normal high impedance condition. If a power-cross or other condition results in excess current flow for an extended period, the thermal failsafe system grounds the line safely and permanently. Backup airgaps are included to insure protection in
the rare instance that the gas tube has vented.
TFS® modules are available in Maximum or Heavy Duty ratings to cover a complete range of telecommunication requirements. They are supplied as a basic component of TII station protectors and as replacement items. Individual modules contain
a No.10 binding post for each side of the protector pair and a ground strap for connection to a ground post. Ground connection should be made with minimum resistance in accordance with best practices as specified for the intended application. Specifications for the TII TFS®
modules are given below.
Dimensions: 0.75" x 0.63" x 2.13"
Weight: 2.2 oz.
Standard Package: 50 Pieces
MODEL DESCRIPTION
TII 355 ( ) Three-Electrode TFS ® Protector Module, Maximum Duty
TII 356L Three-Electrode TFS ® Protector Module, Heavy Duty
TII 356M1 Three-Electrode TFS ® Protector Module, Heavy Duty
Please insert L or M in place of ( ).
* M designates a protector module meeting the REA, PEG and other industry requirements.
* L designates a protector module meeting specific Bell System requirements.
SPECIFICATIONS |
TII 355L TII 356L |
DC Breakdown (Line tc
Ground: |
265 - 600 Volts |
lmpulse Breakdown@
100V/µs |
500V Typical
750V Maximum |
Insulation Resistance @ 100V dc |
> 100 Megohms |
Airgap Breakdown Voltage |
1200 Volts Maximum |
DC Holdover
@52.5V, 260 mA
@135, 200 mA |
Extinguish in < 150 ms |
Impulse Life:
600A, 10/1000us waveform
(300A on each side to ground
simultaneously) either polarity |
50 operations |
Maximum Single
Impulse Discharge Current 8/20 waveform: |
40kA
20kA each side simultaneously |
Short Duration - 60Hz
1000 VAC, 10A, 1 Sec
1000 VAC, 1A, 1 Sec |
5 Operations
60 Operations |
Service
Life:
10Amp,10/1000μsec waveform: 100Amp,10/1000μsec waveform:
300Amp,10/1000μsec waveform: |
1500 Surges Minimum
100 Surges Minimum
50 Surges Minimum |
Capacitance: |
<30pF (L to G) |
Test Method: IEEE 465.1,
TELCORDIA GR-1361 CORE
SPECIFICATIONS |
TII 355M TII 356M1 |
DC Breakdown (Line to Ground) |
300 - 500 Volts |
Impulse Breakdown @ 100V/us |
500V Typical @ 50V Maximum |
Impulse Resistance @ 100V dc |
100 Megohms |
Airgap Breakdown Voltage: |
Meets UL 497A |
DC Holdover: |
150 Volts minimum @ 200 mA |
Impulse Life:
1000A, 10/1000 µsec waveform (500A on each side to ground simultaneously) either polarity |
1000 surges 400 surges
minimum minimum |
Maximum
Single Impulse Discharge Current 8/20 waveform: |
40kA
20kA each side simultaneously |
Service Life: |
1000A, 10/1000
waveshape at one minute intervals each 1000 Surges Minimum polarity,
with 500A on each side to ground simultaneously |
AC Discharge Current 11 Cycles, 60 Hz: |
400Arms 130A rms
(200A each line (65A each line
to ground to ground
simultaneously simultaneously |
Capacitance: |
< 30pF (L to G) |
Test Method: IEEE 465.1,
RUS PE-80