TII Gas Tubes

TII 44 SERIES


TII 44 Heavy Duty Two-Electrode Gas Tube

The TII 44 Heavy Duty Two- Electrode Gas Tube is used to eliminate surge damage to sensitive electronic equipment. Provides low maintenance cost without the problems normally associated with carbon airgap protectors. The TII 44 gas tube is the basic component used in the TII 362M Protector Units.

Dimensions: 0.34' long x 0.30" dia.
Weight: 0.1 oz.
Standard Package: 50 pieces

Model Number 44
DC Breakdown Voltage
300-500
Single Impulse Discharge Current
10 kA
AC Discharge Current 11 Cycles
65 A
Impulse Breakdown Voltage
0.6kV
Impulse Breakdown Waveform v/µsec
100 V
Holdover Voltage @200mA
150 V
Impulse Life 500A @10/1000
400 times
Capacitance
3 pF
DC Arc Voltage
30 V
Glow to Arc Transition Current
1 A
Transition Time
N/A
Listings & Approvals
REA Heavy Duty
Notes
2 Electrode Parallel Plate

comm-omni@comm-omni.com

Return to Comm-Omni Home Page

Index

To speak to one of our consultants, please call us at 1-800-543-8790